Backup power

Battery runtime

Publication date recorded

Estimate how long a battery could run a constant load.

Your inputs

Use a decimal point; commas may group thousands.

Capacity 0–1,000,000,000,000; voltage greater than 0 to 1,000,000; percentages 0–100; load greater than 0 to 1,000,000,000,000.

Your result

Battery runtime

Calculations stay in your browser. Inputs and results are not saved or sent to a server.

How it is calculated

Delivered energy = rated Wh × usable capacity ÷ 100 × efficiency ÷ 100. Runtime in hours = delivered Wh ÷ load in W. For Ah input, rated Wh = V × Ah.

Worked example

500 Wh × 80% × 90% = 360 Wh. At a constant 100 W load, estimated runtime is 3.6 hours.

What to keep in mind

Use the battery manufacturer’s figures. Usable capacity and efficiency are separate reductions. Age, temperature, changing loads and inverter standby draw can shorten actual runtime. This estimate does not confirm equipment compatibility or suitability for essential medical devices.

Calculation reference

Adapted from emonster.tools, with the same calculation methods.

Battery runtime · emonster.tools